PLEASE NOTE: Effective 2019, we no longer supply Control Techniques variable frequency drives and components. We have drives from several other manufacturers which can meet or exceed the performance characteristics of the Control Techniques line. Simply complete the form below, or contact us with the model of your current or obsolete Control Techniques drive and we’ll be glad to identify a suitable replacement.

Also, the Fincor and Saftronics lines of AC variable frequency drives, DC variable speed drives, and reduced voltage starters were once owned by Emerson but have been obsolete for several years. However, we have many years’ experience working with these drives and can quickly identify replacements capable of exceeding the quality and performance of these older drive technologies. For a suitable replacement, fill out the form below or contact us with your drive or application requirements, and we’ll handle it from there!


Unidrive SP

Go to Control Techniques, Solutions Through Innovation

Solutions Platform


Obsolete Drive Replacement RFQ -

If you need a replacement for an existing obsolete drive, complete the following form and we will send you a quote for a suitable replacement.

* Required

Is an encoder or tachometer being used for speed feedback to the drive?:
Opt-In to our e-mail list:

TERMINAL DIAGRAM

Control Techniques Unidrive SP AC Drive Terminal Diagram Connections.

NOTE

*

Thermal protection required. Braking Transisto” is not included in Vnidrive HiHP.

For complete instructions, refer to the Unidrive SP Instruction Manual and User Guide available from local supplier or controltechniques.

  Programmable Analog
  Programmable Digital 
  Non-Programmable

TERMINAL DESCRIPTION

Pin# Function* Type/Description Notes
1 0V Common    
2 +24VDC External Input Back up Power Supply for Control 60W, 24 VDC
3 0V Common Common for External Analog Devices  
4 +10VDC User Supply Reference Supply 10 mA max
5 Analog Input 1 (Local Frequency/Speed Reference) Differential Analog Input, Non-inverting Input, 16 bit +10 VDC 100k Ohms
6 Analog Input 1 (Local Frequency/Speed Reference) Differential Analog Input, Inverting Input 16 bit +10VDC 100k Ohms
7 Analog Input 2 (Remote Frequency/Speed Reference) Single-ended Analog Input 10 bit +10VDC, 100k Ohms or 4-20 mA, 200 Ohms**
8 Analog Input 3 Single-ended Analog Input 10 bit +10 VDC, 100k Ohms or 4-20 mA, 200 Ohms**
9 Analog Output 1 (Frequency/Speed Monitor) Single-ended Analog Output. BI-polar, 10 bit +10VDC or 0-20 / 4-20 mA**
10 Analog Output 2 (Motor Torque Monitor) Single-ended Analog Output, Bi-polar, 10 bit +10VDC or 0-20 / 4-20 mA**
11 OV Common Common External Analog Signals  
21 0V Common    
22 +24 VDC User Output User Supply 200 mA max
23 0V Common Common for External Digital Inputs  
24 Digital I/O 1 (Zero Speed Output) Digital Input/Output 0 to 24 VOC input, or 1 to 24 VDC, 100 mA max output
25 Digital I/O 2 (Reset Input) 100 mA max output Digital Input/Output 0 to 24 VDC input, or 1 to 24 VDC
26 Digital I/O 3 (Run Forward Input) Digital Input/Output 0 to 24 VDC input, or 1 t024VDC, 100 mA max output
27 Digital Input (Run Reverse) Digital Input 0 to 24 VDC, 7.5k Ohms
28 Digital Input (Local/Remote) Digital Input 0 to 24 VDC, 7.5k Ohms
29 Digital Input (Jog) Digital Input 0 to 24 VDC, 7.5k Ohms
30 0V Common Common for External Digital Inputs  
31 Digital Input (Secure Disable) Digital Input 0 to 24 VDC, 1 sec sample
41 Status Relay (Drive Heavy) Normally Open 240 VAC, 2A resistive
42 Status Relay (Drive Heavy) Normally Open 240 VAC, 2A resistive
  Programmable Analog   Programmable Digital

All Analog I/O is scalable

* Values In (parenthesIs) designate default functions. ** 0-20, 4-20 mA modes are also available. See Unidrive SP Manual.