Commander SE

Go to Control Techniques, Solutions Through Innovation

Simplicity with Function

TERMINAL DIAGRAM

Control Techniques Commander SE Terminal Diagram

NOTE

1

Thermal protection required. Not available on Commander SE Size 1

2

Not used for single-phase input

3

Some I/O may be modified via drive
Keypad. Enhanced configuration may be done using SESoft or the optional Universal Keypad.

For complete instructions, refer to the Commander SE User Guide available from local supplier or controltechniques.

Programmable Analog
Programmable Digital 
Non-Programmable
TERMINAL DESCRIPTION
Pin# Function* Type/Description Notes
1 0V Common Common for External Analog Signals
2 Analog Input 1
(Local frequency / Speed Reference), 10 bit
Single-ended
Analog Input
0 to +10 VDC,
100k Ohms,
Sample time 6ms
3 +10 VDC User Supply Reference Supply 5 mA max
Short Circuit Protected
4 0V Common Common for External Digital Signals
5 Analog Input 2
(Remote frequency / Speed Reference), 10 bit
Single-ended
Analog Input
4-20mA** Input,
200 Ohms,
Sample Time 6ms
6 Analog Output 1
(Frequency / Speed), 10 bit
Single-ended
Analog Output
Unipolar
0 to +10 VDC
@ 5 mA max
Update Time 22ms
7 +24 VDC User Supply User Supply 100 mA max
Short Circuit Protected
8 Digital I/O 1
(Zero Speed Output)
Digital
Input / Output
0 to 24 VDC,
7.5k Ohms input or
0 to 24 VDC,
50 mA max output
Update Time 1.5ms
9 Digital Input
(Enable)
Digital Input 0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
10 Digital Input
(Run Forward)
Digital Input 0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
11 Digital Input
(Run Reverse)
Digital Input 0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
12 Digital Input
(Local / Remote Select)
Digital Input 0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
13 Digital Input
(Jog Select)
Digital Input 0 to 24 VDC,
7.5k Ohms
Update Time 1.5ms
14 +24 VDC User Supply User Supply 100 mA max
Short Circuit Protected
15 Status Relay (Drive Healthy) Normally Open 240 VAC, 6A resistive
16 Status Relay (Drive Healthy) Normally Open 240 VAC, 6A resistive
Programmable Analog Programmable Digital

All Analog I/O is scalable

* Values in parenthesis designate default functions.
** 0-20, 20-0, and 20-4 mA are also available. See Commander SE Manual.

Information provided by Control Techniques, a world leader in the design, production and marketing of electronic drives for the control of electric motors.

Print Friendly, PDF & Email