ABB - ACS150 AC Variable Frequency Component DrivesABB General Machinery Drives
ACS350, 0.5hp to 10hp Technical Guide

Technical specification

ACS350

01U

02A4

2

+

J404

Input connection
Voltage and power range 1-phase, 200 to 240 V +10%
0.37 to 2.2 kW (0.5 to 3 hp)
3-phase, 200 to 240 V +10%
0.37 to 4 kW (0.5 to 5 hp)
3-phase, 380 to 480 V +10%
0.37 to 7.5 kW (0.5 to 10 hp)
Frequency  48 to 63 Hz
Power factor 0.98
Output connection
Voltage  3-phase, from 0 to Usupply
Frequency  0 to 500 Hz
Continuous loading capability
(constant torque at a max. ambient temperature 40°C)
Rated output current I2N
Overload capability
(at a max. ambient temperature of 40°C)
1.5 x I2N for 1 minute every 10 minutes
1.8 x I2N for 2 s every 10 minutes
Switching frequency
Default
Selectable
4 kHz
4 to 12 kHz with 4 kHz steps
Acceleration time 0.1 to 1800 s
Deceleration time 0.1 to 1800 s
Braking Brake chopper-standard (100% braking capability)
Environmental limits
Ambient temperature -10 to 40°C (14 to 104°F), no frost allowed,
50°C (122°F) with 10% derating
Altitude
Output current
Rated current available at 0 to 1000 m
(0 to 3281 ft) reduced by 1% per 100 m
(328 ft) over 1000 to 2000 m (3281 to 6562 ft)
Relative humidity Lower than 95% (without condensation)
Protection class IP 20 / Protected Chassis
Enclosure color NCS 1502-Y, RAL 9002, PMS 420 C
Contamination levelsTransportationStorage

Operation

IEC721-3-3
No conductive dust allowed
Class 1C2 (chemical gases)
Class 1S2 (solid particles)
Class 2C2 (chemical gases)
Class 2S2 (solid particles)
Class 3C2 (chemical gases)
Class 3S2 (solid particles)
Programmable control connections
Two analog inputs
Voltage signal
Unipolar  
Bipolar  
Current signal
Unipolar  
Bipolar  
Potentiometer reference
value
Resolution
Accuracy
0 (2) to 10 V, Rin > 312 k Ohm
-10 to 10 V, Rin > 312 k Ohm0 (4) to 20 mA, Rin = 100 Ohm
-20 to 20 mA, Rin > 100 Ohm
10 V +1% max. 10 mA, R < 10 k Ohm
0.1 %
+1%
One analog output 0 (4) to 20 mA, load < 500 Ohm
Auxiliary voltage 24 V DC +10%, max. 200 mA
Five digital inputsInput impedance 12 to 24 V DC with internal or external supply, PNP and NPN, pulse train 0 to 16 kHz.
2.4 k Ohm
One relay output
Type
Maximum switching voltage
Maximum switching current
Maximum continuous current
NO + NC
250 V AC/30 V DC
0.5 A/30 V DC; 5 A/230 V AC
2 A rms
One digital output
Type
Maximum switching voltage
Maximum switching current
Frequency
Resolution
Accuracy
Transistor output
30 V DC
100 mA/30 V DC, short circuit
protected
10 Hz to 16 kHz
1 Hz
0.2%
Serial communication
Fieldbuses
Refresh rate
Plug-in type
< 10 ms (between drive and fieldbus module)
PROFIBUS DP 9-pin D-connector
Baud rate up to 12 Mbit/s
PROFIBUS DP and PROFIBUS DPV1
Network side based on “PROFldrive” profile.
DeviceNet 5-pin screw type connector
Baud rate up to 500 kbit/s
Network side based on ODVA “AC/DC drive” profile.
CANopen 9-pin D-connector
Baud rate up to 1 Mbit/s
Network side based on CiA DS402 profile.
Modbus 4-pin screw type connector
Baud rate up to 115 kbit/s
Product compliance
Low voltage Directive 73/23/EEC with supplements
Machinery Directive 98/37/EC
EMC Directive 89/336/EEC with supplements
Quality assurance system ISO 9001
Environmental system ISO 14001
UL, cUL, and CE approvals
EMC (according to EN61800-3)
2nd environment filter, unrestricted distribution with 30 m (98 ft) cable- standard.

ABB Inc.

ABB Inc.
Low Voltage Drives
16250 W. Glendale Drive
New Berlin, WI 53151
ABB Inc.
Drives & LVC Canada
3299 J.B. Deschamps Blvd.
Lachine, Quebec H8T 3E4
Telephone
Fax
Internet
 (800) 752-0696
(262) 785-0397
http://www.abb.us/drives
Telephone
Fax
Internet
 (800) 215-3006
(514) 420-3137
http://www.abb.com/motors&drives
http://www.abb-drives.com

© 2006 ABB Inc. ACS350-PHTC01U-EN REV B, Effective: 1/1/06.