ABB Component Drives
ACS150, 0.5hp to 5hp Technical Guide
- ABB ACS150 Component Drives
- Technical Specifications
- Ratings, Types, Voltages and Construction
Notes for Product Selection
240VAC Ratings (prices)
480VAC Ratings (prices) - Dimensions, Weight and Noise
- Interface and Options (prices)
- Technical Data
- Control Connections
Technical data
Cooling |
The ACS150 is configured with cooling fans as standard. The cooling air must be free from corrosive materials and must not be above the maximum ambient temperature of 40°C (50°C with derating). For more specific limits see the Technical specification – Environmental limits in this catalog. |
Cooling air flow
Type Code | Frame Size | Heat Dissipation | Air Flow | ||
W | BTU/Hr | m3/h | ft3/min | ||
1-phase supply voltage 200 – 240 V units | |||||
ACS150-01U-02A4-2 | R0 | 25 | 85 | -* | -* |
ACS150-01U-04A7-2 | R1 | 46 | 157 | 24 | 14 |
ACS150-01U-06A7-2 | R1 | 71 | 242 | 24 | 14 |
ACS150-01U-07A5-2 | R2 | 73 | 249 | 21 | 12 |
ACS150-01U-09A8-2 | R2 | 96 | 328 | 21 | 12 |
3-phase supply voltage 200 – 240 V units | |||||
ACS150-03U-02A4-2 | R0 | 19 | 65 | -* | -* |
ACS150-03U-03A5-2 | R0 | 31 | 106 | -* | -* |
ACS150-03U-04A7-2 | R1 | 38 | 130 | 24 | 14 |
ACS150-03U-06A7-2 | R1 | 60 | 205 | 24 | 14 |
ACS150-03U-07A5-2 | R1 | 62 | 212 | 21 | 12 |
ACS150-03U-09A8-2 | R2 | 83 | 283 | 21 | 12 |
3-phase supply voltage 380 – 480 V units | |||||
ACS150-03U-01A2-4 | R0 | 11 | 38 | -* | -* |
ACS150-03U-01A9-4 | R0 | 16 | 55 | -* | -* |
ACS150-03U-02A4-4 | R0 | 21 | 72 | -* | -* |
ACS150-03U-03A3-4 | R1 | 31 | 106 | 13 | 8 |
ACS150-03U-04A1-4 | R1 | 40 | 137 | 13 | 8 |
ACS150-03U-05A6-4 | R1 | 61 | 208 | 19 | 11 |
ACS150-03U-08A8-4 | R1 | 94 | 321 | 24 | 14 |
* Frame size RO with free convection cooling. |
Free space requirements
Enclosure Type | Space Above mm/in | Space Below mm/in | Space on Left/Right mm/in |
All Frame Sizes | 80/3.15 | 80/3.15 | 0/0 |
Fuses |
Standard semi-conductor fuses can be used with the ACS150. Recommended fuse ratings are show in the table below. |
Selection table
Type Code | Frame Size | IEC Fuses | UL Fuses | ||
A | Fuse Type* | A | Fuse Type* | ||
1-phase supply voltage 200 – 240 V units | |||||
ACS150-01U-02A4-2 | R0 | 10 | gG | 10 | UL class T |
ACS150-01U-04A7-2 | R1 | 16 | gG | 20 | UL class T |
ACS150-01U-06A7-2 | R1 | 20 | gG | 25 | UL class T |
ACS150-01U-07A5-2 | R2 | 25 | gG | 30 | UL class T |
ACS150-01U-09A8-2 | R2 | 35 | gG | 35 | UL class T |
3-phase supply voltage 200 – 240 V units | |||||
ACS150-03U-02A4-2 | R0 | 10 | gG | 10 | UL class T |
ACS150-03U-03A5-2 | R0 | 10 | gG | 10 | UL class T |
ACS150-03U-04A7-2 | R1 | 10 | gG | 10 | UL class T |
ACS150-03U-06A7-2 | R1 | 16 | gG | 15 | UL class T |
ACS150-03U-07A5-2 | R1 | 16 | gG | 15 | UL class T |
ACS150-03U-09A8-2 | R2 | 16 | gG | 20 | UL class T |
3-phase supply voltage 380 – 480 V units | |||||
ACS150-03U-01A2-4 | R0 | 10 | gG | 10 | UL class T |
ACS150-03U-01A9-4 | R0 | 10 | gG | 10 | UL class T |
ACS150-03U-02A4-4 | R0 | 10 | gG | 10 | UL class T |
ACS150-03U-03A3-4 | R1 | 10 | gG | 10 | UL class T |
ACS150-03U-04A1-4 | R1 | 16 | gG | 15 | UL class T |
ACS150-03U-05A6-4 | R1 | 16 | gG | 15 | UL class T |
ACS150-03U-08A8-4 | R1 | 20 | gG | 25 | UL class T |
* According to IEC-60269 standard. |
ABB Inc. Low Voltage Drives 16250 W. Glendale Drive New Berlin, WI 53151 | ABB Inc. Drives & LVC Canada 3299 J.B. Deschamps Blvd. Lachine, Quebec H8T 3E4 | ||
Telephone Fax Internet | (800) 752-0696 (262) 785-0397 http://www.abb.us/drives | Telephone Fax Internet | (800) 215-3006 (514) 420-3137 http://www.abb.com/motors&drives http://www.abb-drives.com |
© 2006 ABB Inc. ACS150-PHTC01U-EN REV B, Effective: 12/1/05.
Specifications subject to change without notice.