ABB ACS800 AC DRIVES

0.5 to 100Hp @ 208 to 240V
1.5 to 600Hp @ 380 to 500V

380V Ratings
3-phase supply voltage 380, 400, 415, 440, 460, 480 or 500 V – Power ratings are valid at nominal voltage, 400 V (50Hz power line)

Type Code
NEMA 1 (6,7)
I max
A (3)

Nominal Ratings (4, 5)

Frame
Size
Price
Normal Duty (VT) (1)
(110% I2N)
Heavy-duty (CT) (2)
(150% I2hd)
I 2N
A
P N
kW (8)
I 2hd
A
P hd
kW (8)
Wall Mounted Drives
ACS800-U1-0004-5 6.5 4.5 1.5 3.4 1.1 R2 CALL
ACS800-U1-0005-5 8.2 5.6 2.2 4.2 1.5 R2 CALL
ACS800-U1-0006-5 10.8 7.7 3 5.6 2.2 R2 CALL
ACS800-U1-0009-5 13.8 10 4 7.5 3 R2 CALL
ACS800-U1-0011-5 17.6 12 5.5 9.2 4 R2 CALL
ACS800-U1-0016-5 24 18 8 13 6 R3 CALL
ACS800-U1-0020-5 32 23 11 18 8 R3 CALL
ACS800-U1-0025-5 46 31 15 23 11 R3 CALL
ACS800-U1-0030-5 62 39 18.5 32 15 R4 CALL
ACS800-U1-0040-5 72 44 22 36 18.5 R4 CALL
ACS800-U1-0050-5 86 61 30 50 22 R5 CALL
ACS800-U1-0060-5 112 75 37 60 30 R5 CALL
ACS800-U1-0070-5 138 88 45 69 37 R5 CALL
ACS800-U1-0100-5 164 115 55 88 45 R6 CALL
ACS800-U1-0120-5 202 145 75 113 55 R6 CALL
ACS800-U1-0140-5 282 163 90 141 75 R6 CALL
Free Standing Drives w/Extension Enclosure
ACS800-U2-0170-5 326 192 90 162 90 R7 CALL
ACS800-U2-0210-5 404 240 132 192 90 R7 CALL
ACS800-U2-0260-5 432 284 160 224 110 R7 CALL
ACS800-U2-0320-5 568 361 200 284 160 R8 CALL
ACS800-U2-0400-5 720 477 250 361 200 R8 CALL
ACS800-U2-0440-5 904 515 250 477 250 R8 CALL
ACS800-U2-0490-5 1017 590 315 515 (10) 250 R8 CALL
ACS800-U2-0550-5 1017 632 355 590 (10) 315 R8 CALL
ACS800-U2-0610-5 1017 704 400 590 (10) 315 R8 CALL
For your specific application contact us for pricing.
Cabinet Drives
ACS800-U2-0170-5+C111 +P901 +H358 326 192 90 162 90 R7 CALL
ACS800-U2-0210-5+C111 +P901 +H358 404 240 132 192 90 R7 CALL
ACS800-U2-0260-5+C111 +P901 +H358 432 284 160 224 110 R7 CALL
ACS800-U2-0320-5+C111 +P901 +E208+H358 568 361 200 284 160 R8 CALL
ACS800-U2-0400-5+C111 +P901 +E208+H358 720 477 250 361 200 R8 CALL
ACS800-U2-0440-5+C111 +P901 +E208+H358 904 515 250 477 250 R8 CALL
ACS800-U2-0490-5+C111 +P901 +E208+H358 1017 590 315 515 (10) 250 R8 CALL
ACS800-U2-0550-5+C111 +P901 +E208+H358 1017 632 355 590 (10) 315 R8 CALL
ACS800-U2-0610-5+C111 +P901 +E208+H358 1017 704 400 590 (10) 315 R8 CALL
Note: All drives are supplied w/Operator Control Panel.

For your specific application contact us for pricing.

NOTES

  1. I2N: continuous base current at 40°C (104°F). Overload cycle 110% I2N for 1 minute / 5 minutes allowed at 40°C (104°F).
  2. I2hd: continuous base current at 40°C (104°F). Overload cycle 150% I2hd for 1 minute / 100% 5 minutes allowed at 40°C (104°F).
  3. 1max: current available for 10 seconds at start.
  4. Current ratings do not change with different supply voltages.
  5. The rated current of the ACS 800 must be greater than or equal to the rated motor current to achieve the rated motor power given in the table.
  6. All -U1 models -0004 through -0140 come with a conduit box as standard.
  7. All-02 models -0170 through -0610 with added option codes come with bottom entry I exit, US conduit plate (H358) and common mode filters (E208) for drives -0320 and larger. The extended enclosure (C111) adds a fusible disconnect with power cabie entry and exit remaining bottom / bottom. If European conduit plate is desired, delete option H358 with no price change.
  8. Kilowatt rating is based upon IEC ratings for most 2,4 and 6-pole motors (3000, 1500, 1000 rpm). Check motor nameplate current for compatibility.
  9. When ordering 380V IP54 R6 units, order as ACS800-01-xxxx-5+B056+H358 (NOTE: This unit will NOT ship w/ a UL label).
  10. 140% I2hd overload current for 1 minute / 5 minutes if the ambient temperature is 40°C. 150% I2hd overload current for 1 minute / 5 minutes @ 30°C.

© 2004 ABB Inc. All rights reserved Specification and pricing subject to change without notice.

ACS800-US-03
Rev. B

Effective: 06/11/03
Supersedes: 10/07/02