ABB ACS800 AC DRIVES
0.5 to 100Hp @ 208 to 240V
1.5 to 600Hp @ 380 to 500V
- Overview
- Standard Features / Available Options and Software
- Specifications
- Basic Type Code Information
- 230V Ratings (prices)
- 380V Ratings (prices)
- 460V Ratings (prices)
- ACS 800-U2 NEMA 1 R7 & R8 Frame Size and
ACS 800-02+C111 IP21 (NEMA 1) R7 & R8 Frame Size - ACS 800 NEMA 1/12 R2 through R6 Frame Size
- ACS 800-02 NEMA 1 R7 & R8 Frame Size
- ACS 800-U4 Module R7 Frame Size
- ACS 800-U4 Module R8 Frame Size
ACS 800 Specifications
Input Connection | ||
Input Voltage (U1) | 208/220/230/240 VAC 3-phase +/-10% for 200 VAC units 380/400/415/440/460/480/500 VAC 3-phase +/-10% for 480 VAC units | |
Input Frequency | 48 to 63 Hz, maximum rate of change 17%/second | |
Line Imbalance | Max +/-3% of nominal phase to phase input voltage | |
Fundamental Power Factor (cos�) Connection | 0.98 (at nominal load) | |
Output Connection | ||
Output Voltage | 0 to U1 3-phase symmetrical, UN at the field weakening point | |
Output Frequency | -300 to +300 Hz, in DTC mode (0-3.2((U1 input voltage/UN motor)*fN motor)) | |
Frequency Resolution | 0.01 Hz | |
Continuous Current | 1.0 * I2N (normal use) 1.0 * I2hd (heavy-duty use) | |
Short Term Overload Capacity | INmax = 1.1 * I2N (1 min /5 minutes @ 40°C), typical INhdmax = 1.5 * I2hd (at least 1 min / 5 min @ 40°C) | |
Peak Overload Capacity | 1max (400 VAC and 500 VAC) (at least 10 seconds at start) | |
Field Weakening Point | 8 to 300 Hz | |
Switching Frequency | 3 kHz (average) | |
Acceleration Time | 0 to 1800 s | |
Deceleration Time | 0 to 1800 s | |
Efficiency | 98% at nominal power level | |
Short Circuit Withstand Rating | 65,000 AIC (UL) R2-R8 | |
Connection | U2, V2, W2 | |
Ambient Conditions, Operation | ||
Air Temperature | 0° to 40°C (104°F), above 40°C the maximum output current is de-rated 1% for every additional 1°C (up to 50°C (122°F) maximum limit) | |
Relative Humidity | 5 to 95%, no condensation allowed, maximum relative humidity is 60% in the presence of corrosive gasses | |
Contamination Levels | ||
IEC | 60721-3-1,60721-3-2 and 60721-3-3 | |
Chemical Gasses | 3C1 (w/o coating), 3C2 (with coating) | |
Solid Particles | 3S2 | |
Installation Site Altitude | 0 to 1000 m (3300 ft) above sea level. At sites over 1000 m above sea level, the maximum power is de-rated 1 % for every additional 1 00 m (330 ft). If the installation site is higher than 2000 m above sea level, please contact your local ABB distributor or representative for further information. | |
Vibration | Max 1 mm (0.04″) 5 to 13.2 Hz, Max 7 m/s2 (23 ft/s2) 13.2 to 100 Hz sinusoidal | |
Ambient Conditions, Storage | ||
Air Temperature | -20° to 70°C (-4 ° to 158°F) | |
Relative Humidity | Less than 95%, no condensation allowed | |
Atmospheric Pressure | 70 to 106 kPa (10.2 to 15.4 PSI) | |
Vibration | Max 1 mm (0.04″) 5 to 13.2 Hz, Max 7 m/s2 (23 ft/s2) 13.2 to 100 Hz | |
Shock (IEC 60068-2-29) | Max 100 m/s2 (330 ft/s2) 11 ms | |
Ambient Conditions, Transportation | ||
Air Temperature | -20 to 70 C (-4 to 158 F) | |
Relative Humidity | Max 95% | |
Atmospheric Pressure | 60 to 106 kPa (8.7 to 15.4 PSI) | |
Vibration | Max 3.5 mm (0.14″) 2 to 9 Hz, Max 15 m/s2 (49 ft/s2) 9 to 200 Hz sinusoidal | |
Shock (IEC 60068-2-29) | Max 100 m/s2 (330 ft/s2) 11 ms | |
Free Fall | 250 mm (weight under 100 kg) 100 mm (weight over 100 kg) | |
Cooling Information | ||
Cooling Method | Internal Fan | |
Power Loss | Approximately 3% of rated power | |
Auxiliary Power Supply | ||
Voltage | 24 VDC, +/- 10% | |
Maximum Current | 250 mA | |
Protection | Short Circuit Protection | |
Terminal Block Size | 0.3 to 3 mm2 (12 to 22 AWG) | |
Analog Inputs | ||
Two Programmable Differential Current Inputs | ||
Signal Level | 0 (4) to 20mA | |
Input Resistance | R1 = 100 ohms | |
One Programmable Differential Voltage Input | ||
Signal Level | -10 VDC 0 (2) VDC to +10 VDC | |
Input Resistance | R1 = 200 k-ohms | |
Common Mode Voltage | +/-15 VDC, max. | |
Common Mode Rejection Ratio | > 60 dB at 50 Hz | |
Resolution | 0.025% (12 bit) | |
Accuracy +/- 0.5% | ||
Input Updating Time | 6 ms (Standard Application Software) | |
Terminal Block Size | Cables 0.3 to 3.3 mm2 (12 to 22 AWG) | |
Optional Isolation | Available through external Module | |
Reference Power Supply | ||
Voltage | +10 VDC, 0, -10 VDC +/- 0.5% at 25 C (77 F) | |
Maximum Load | 10mA | |
Applicable Potentiometer | 1 k-ohm to 10 k-ohm | |
Terminal Block Size | Cables 0.3 to 3.3 mm2 (12 to 22 AWG) | |
Analog Outputs | ||
Two Programmable Current Outputs | ||
Signal Level | 0 (4) to 20 mA | |
Resolution | 0.025% (12 bit) | |
Accuracy | +/-1% Full Scale Range) at 25 C (77 F), temperature coefficient +/- 200 ppm/C (+/- 111 ppm/F) max. | |
Maximum Load Impedance | 700 ohms | |
Output Updating Time | 24 ms, max | |
Terminal Block Sizes | Cables 0.3 to 3.3 mm2 (12 to 22 AWG) | |
Digital Inputs | ||
Six Programmable Digital Inputs (Common Ground), plus One Start Interlock | ||
Isolation | Isolated, can be divided in two isolated groups | |
Isolation Test Voltage | 500 VAC, 1 minute | |
Terminal Block Size | Cables 0.3 to 3.3 mm2 (12 to 22 AWG) | |
Signal Level | 24 VDC, -15% to +20% | |
Logical Thresholds | < 8 VDC at “0”, >12 VDC at “1” | |
Input Current | 10 mA, Digital Input 1 to Digital Input 5, 5 mA Digital Input 6 | |
Filtering Time Constant | 1 ms | |
Input Updating Time | 6 ms | |
Internal 24 VDC Supply for Digital Inputs | ||
Voltage | 24 VDC | |
Maximum Current | 100 mA | |
Connector | X22:7 | |
Protection | Short Circuit Proof | |
An external 24 VDC supply may be used instead of the internal supply | ||
Relay Outputs | ||
Three Programmable Relay Outputs | ||
Switching Capacity | 8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC | |
Maximum Continuous Current | Ic = 2 A RMS | |
Contact Material | Silver Cadmium Oxide (AgCdO) | |
Isolation Test Voltage | 4 kVAC, 1 minute | |
Terminal Block Size | Cables 0.3 to 3.3 mm2 (12 to 22 AWG) | |
Output Updating Time | 100 ms | |
Protections | ||
Single Phase | Protected (input & output) | |
Overvoltage Trip Limit | 1.3 * V1max | |
Undervoltage Trip Limit | 0.65 * V1min | |
Overtemperature | 140°C (284°F) | |
Auxiliary Voltage | Short Circuit Protected | |
Ground Fault | Protected | |
Microprocessor Fault | Protected | |
Motor Stall Protection | Protected | |
Motor Overtemperature Protection (I2t) | Protected |
U1 = lnput Voltage
UN = Nominal Motor Voltage
fN = Nominal Motor Frequency
I2N = Nominal Current – Normal Duty
IMax = Maximum Current for Peak Overload
SN = Power – Normal Duty (kVA)
PN = Power – Normal Duty (kW)
PN = Power – Normal Duty (HP)
I2hd = Nominal Current – Heavy-Duty
SNhd = Power (kVA) – Heavy-Duty
PNhd = Power (kW) – Heavy-Duty
PNhd = Power (HP) – Heavy-Duty
Contact Joliet Technologies for Custom Drive Pricing.
Phone: (815) 725-9696 or
Toll Free: (866) 492-9888
Fax: (815) 725-9393
E-mail: info@joliettech.com
RFQ – Request for Quote
© 2004 ABB Inc. All rights reserved Specification and pricing subject to change without notice.
ACS800-US-03 Rev. B | Effective: 06/11/03 |