Technical data

Mains connection
Voltage and
power range
3-phase, UN2 = 208 to 240 V, +10/-15% (-01)
3-phase, UN5 = 380 to 500 V, +10/-15% (-01), ±10% (-07,-17,-37)
3-phase, UN7 = 525 to 690 V, +10/-15% (-01), ±10% (-07,-17,-37)
0.75 to 350 hp (0.55 to 250 kW) (-01)
60 to 3000 hp (45 to 2800 kW) (-07)
250 to 3300 hp (250 to 3200 kW) (-17,-37)
Frequency  50/60 Hz ±5%
Power factor cosφ1 = 0.98 (fundamental)
cosφ = 0.93 to 0.95 (total)
Efficiency (at
nominal power)
 98%
Motor connection
Voltage 3-phase output voltage 0 to UN2 /UN3 /UN5 /UN7
Frequency 0 to ±500 Hz 1) 2)
Motor control Direct torque control (DTC)
Torque control:
Open loop
Closed loop
Torque step rise time:
<5 ms with nominal torque
<5 ms with nominal torque
Non-linearity:
± 4% with nominal torque
± 3% with nominal torque
Open loop
Closed loop
Speed control:
Open loop
Closed loop
Static accuracy:
10% of motor slip
0.01% of nominal speed
Dynamic accuracy:
0.3 to 0.4% seconds with 100% torque step
0.1 to 0.2% seconds with 100% torque step
Open loop
Closed loop
Product compliance
– CE
– Low Voltage Directive 2006/95/EC
– Machinery Directive 2006/42/EC
– EMC Directive 2004/108/EC
– Quality assurance system ISO 9001 and Environmental system ISO 14001
– RoHS
– UL, cUL 508A or cUL 508C and CSA C22.2 NO.14-10, C-Tick, EAC 4)
– Functional safety: STO TÜV Nord certificate
– ATEX-certified Safe Disconnection Function, Ex II (2) GD 5)
– Marine type approvals for -01
EMC according to EN 61800-3:2004 + A1:2012
Categories C3 and C2 with internal option
Environmental limits
 Ambient temperature
Transport
Storage
Operation (air-cooled
-40 to +70 °C
-40 to +70 °C
-15 to +55 °C, no frost allowed (-01)
0 to +50 °C, no frost allowed (-07, -17, -37)
+40 to 55 °C with derating (-01) 3)
+40 to 50 °C with derating of 1%/1 °C (-07,-17,-37)
Cooling method
Air-cooled Dry clean air
Altitude
0 to 1,000 m
1,000 to 4,000 m
Without derating
With derating of 1%/100 m 6)
Relative humidity 5 to 95%, no condensation allowed
Degree of protection
IP20
IP21
IP22
IP42, IP54
IP55
Option (-01)
Standard (-01)
Standard (-07, -17, -37)
Option (-07, -17, -37)
Option (-01)
Paint color RAL 9017/9002 (-01), RAL 9017/7035 (-07, -17, -37)
Contamination levels No conductive dust allowed
Storage IEC 60721-3-1, Class 1C2 (chemical gases),
Class 1S2 (solid particles)
Transportation IEC 60721-3-2, Class 2C2 (chemical gases),
Class 2S2 (solid particles)
Operation IEC 60721-3-3, Class 3C2 (chemical gases), Class 3S2 (solid particles)
Functional safety
Standard Safe torque off (STO according EN/IEC 61800-5-2)
IEC 61508 ed2: SIL 3, IEC 61511: SIL 3, EN/IEC 62061: SIL CL 3, EN ISO 13849-1: PL e
With internal safety
option safety functions
module
Safe stop 1 (SS1), safely-limited speed (SLS), safe
stop emergency (SSE), safe brake control, (SBC)
and safe maximum speed (SMS), prevention of unexpected startup (POUS), Safe direction (SDI),
Safe speed monitor (SSM), EN/IEC 61800-5-2,
IEC 61508 ed2: SIL 3, IEC 61511: SIL 3,
EN/IEC 62061: SIL CL 3, EN ISO 13849-1: PL e
TÜV Nord certified
Fieldbus
communication
PROFIsafe over profinet, certified
C = Chemically active substances
S = Mechanically active substances
1) For higher operational output frequencies please contact your local ABB offi ce
2) Operation above 120 Hz might require type specific derating, please contact your local ABB office
3) Please see pages 12 to 13 for further details
4) EAC has replaced GOST R
5) Codes +L513/+L514, +Q971 for -07, -17,- 37
6) Derating reduced by lower than 40 oC ambient temperature

© Copyright 2015 ABB. All rights reserved.
Specifications subject to change without notice.