Low voltage AC drives
ABB industrial drives
ACS880, single drives
0.75 to 1700 hp (0.55 to 1300 kW)
- The all-compatible ACS880 series drives
- How to select a drive
- Technical data
- Wall-mounted single drives, ACS880-01
- Main features
- Ratings, types and voltages (230 V)
- Ratings, types and voltages (500 V)
- Ratings, types and voltages (600 V)
- Dimensions
- Standard interface and extensions for comprehensive connectivity
- Standard software for scalable control and functionality
- Intuitive human-machine interface
- Integrated safety simplifies configuration
- Flexible connectivity to automation networks
- Input/output extension modules for increased connectivity
- Speed feedback interfaces for precise process control
- DDCS communication option modules
Technical data
Mains connection | |
Voltage and power range |
3-phase, UN2 = 208 to 240 V, +10/-15% (-01) 3-phase, UN5 = 380 to 500 V, +10/-15% (-01), ±10% (-07,-17,-37) 3-phase, UN7 = 525 to 690 V, +10/-15% (-01), ±10% (-07,-17,-37) 0.75 to 350 hp (0.55 to 250 kW) (-01) 60 to 3000 hp (45 to 2800 kW) (-07) 250 to 3300 hp (250 to 3200 kW) (-17,-37) |
Frequency | 50/60 Hz ±5% |
Power factor | cosφ1 = 0.98 (fundamental) cosφ = 0.93 to 0.95 (total) |
Efficiency (at nominal power) |
98% |
Motor connection | |
Voltage | 3-phase output voltage 0 to UN2 /UN3 /UN5 /UN7 |
Frequency | 0 to ±500 Hz 1) 2) |
Motor control | Direct torque control (DTC) |
Torque control: Open loop Closed loop |
Torque step rise time: <5 ms with nominal torque <5 ms with nominal torque Non-linearity: ± 4% with nominal torque ± 3% with nominal torque |
Open loop Closed loop |
|
Speed control: Open loop Closed loop |
Static accuracy: 10% of motor slip 0.01% of nominal speed Dynamic accuracy: 0.3 to 0.4% seconds with 100% torque step 0.1 to 0.2% seconds with 100% torque step |
Open loop Closed loop |
|
Product compliance | |
– CE | |
– Low Voltage Directive 2006/95/EC | |
– Machinery Directive 2006/42/EC | |
– EMC Directive 2004/108/EC | |
– Quality assurance system ISO 9001 and Environmental system ISO 14001 | |
– RoHS | |
– UL, cUL 508A or cUL 508C and CSA C22.2 NO.14-10, C-Tick, EAC 4) | |
– Functional safety: STO TÜV Nord certificate | |
– ATEX-certified Safe Disconnection Function, Ex II (2) GD 5) | |
– Marine type approvals for -01 | |
EMC according to EN 61800-3:2004 + A1:2012 | |
Categories C3 and C2 with internal option | |
Environmental limits | |
Ambient temperature | |
Transport Storage Operation (air-cooled |
-40 to +70 °C -40 to +70 °C -15 to +55 °C, no frost allowed (-01) 0 to +50 °C, no frost allowed (-07, -17, -37) +40 to 55 °C with derating (-01) 3) +40 to 50 °C with derating of 1%/1 °C (-07,-17,-37) |
Cooling method | |
Air-cooled | Dry clean air |
Altitude | |
0 to 1,000 m 1,000 to 4,000 m |
Without derating With derating of 1%/100 m 6) |
Relative humidity | 5 to 95%, no condensation allowed |
Degree of protection | |
IP20 IP21 IP22 IP42, IP54 IP55 |
Option (-01) Standard (-01) Standard (-07, -17, -37) Option (-07, -17, -37) Option (-01) |
Paint color | RAL 9017/9002 (-01), RAL 9017/7035 (-07, -17, -37) |
Contamination levels | No conductive dust allowed |
Storage | IEC 60721-3-1, Class 1C2 (chemical gases), Class 1S2 (solid particles) |
Transportation | IEC 60721-3-2, Class 2C2 (chemical gases), Class 2S2 (solid particles) |
Operation | IEC 60721-3-3, Class 3C2 (chemical gases), Class 3S2 (solid particles) |
Functional safety | |
Standard | Safe torque off (STO according EN/IEC 61800-5-2) IEC 61508 ed2: SIL 3, IEC 61511: SIL 3, EN/IEC 62061: SIL CL 3, EN ISO 13849-1: PL e |
With internal safety option safety functions module |
Safe stop 1 (SS1), safely-limited speed (SLS), safe stop emergency (SSE), safe brake control, (SBC) and safe maximum speed (SMS), prevention of unexpected startup (POUS), Safe direction (SDI), Safe speed monitor (SSM), EN/IEC 61800-5-2, IEC 61508 ed2: SIL 3, IEC 61511: SIL 3, EN/IEC 62061: SIL CL 3, EN ISO 13849-1: PL e TÜV Nord certified |
Fieldbus communication |
PROFIsafe over profinet, certified |
C = Chemically active substances S = Mechanically active substances 1) For higher operational output frequencies please contact your local ABB offi ce 2) Operation above 120 Hz might require type specific derating, please contact your local ABB office 3) Please see pages 12 to 13 for further details 4) EAC has replaced GOST R 5) Codes +L513/+L514, +Q971 for -07, -17,- 37 6) Derating reduced by lower than 40 oC ambient temperature |
© Copyright 2015 ABB. All rights reserved.
Specifications subject to change without notice.